Jackwell Technology Co.,Ltd
|
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
1. Standby power: 484.0 KW
2. Engine Make & Model:Perkins 2806A-E18TAG1
3.Cooling Method: Water
4.GoverningType: Electronic Governing
5.Class: ISO 8528 G2
6.Compression Ratio:14.5:1
7.Displacement: l (cu.in) 18.1 (1104.5)
4 Stroke 550kVA Perkins Diesel Generator, P605E5
Output Ratings |
|
Generating Set Model |
* P605E5 Prime* Standby* |
380-415V,50Hz |
550.0 kVA 605.0 kVA 440.0 kW 484.0 kW |
220/127V, 60 Hz |
- - - - |
Ratings at 0.8 power factor.
Technical Data |
|
Engine Make & Model: |
Perkins 2806A-E18TAG1 |
Alternator Model: |
LL6114G |
Base Frame Type: |
Heavy Duty Fabricated Steel |
Circuit Breaker Type: |
3 Pole ACB/MCCB |
Frequency: |
50 Hz 60 Hz |
Engine Speed: RPM |
1500 - |
Fuel Tank Capacity: litres (US gal) |
1000 (264.2) |
Fuel Consumption P550P5 : l/hr (US gal/hr) |
110.8 (29.3) - |
Fuel Consumption P605E5 : l/hr (US gal/hr) |
122.5 (32.4) - |
P550P5 / P605E5
Engine Technical Data
Physical Data
Manufacturer: Perkins
Model: 2806A-E18TAG1
No. of Cylinders/Alignment: 6 / In Line
Cycle: 4 Stroke
Induction: Turbo charged Air To Air Charge Cooled
Cooling Method: Water Governing
Type: Electronic
Governing Class: ISO 8528 G2
Compression Ratio: 14.5:1
Displacement: l (cu.in) 18.1 (1104.5)
Bore/Stroke: mm (in) 145.0 (5.7)/183.0 (7.2)
Moment of Inertia: kg m² (lb. in²) 7.44 (25424)
Engine Electrical System:
-Voltage/Ground: 24/Negative
-Battery Charger Amps: 70
Weight: kg (lb)
- Dry: 2050 (4519)
- Wet: 2158 (4758)
Air System 50 Hz 60 Hz
Air Filter Type:Replaceable Element Combustion
Air Flow:m³/min (cfm)
-Standby: 24.9 (879)
-Prime: 22.8 (805)
- Max. Combustion Air Intake Restriction: kPa (in H2O) 6.3 (25.3)
- Radiator Cooling Air Flow: m³/min (cfm) 660.0 (23308)
- External Restriction to Cooling Air Flow: Pa (in H2O) 125 (0.5)
Cooling System 50 Hz 60 Hz
Cooling System Capacity: (US gal) 61.0 (16.1)
- Water Pump Type: Centrifugal
Heat Rejected to Water &Lube Oil: kW (Btu/min)
-Standby: 138.7 (7888)
-Prime: 133.3 (7581)
- Heat Radiation to Room:
kW (Btu/min)
-Standby: 34.5 (1962)
-Prime: 30.9 (1757)
- Radiator Fan Load: kW (hp) 8.0 (10.7)
Cooling system designed to operate in ambient conditions up to 50°C (122°F).
Contact your local FG Wilson dealer for power ratings at specific site conditions.
Performance 50 Hz 60 Hz
Engine Speed: RPM 1500
- Gross Engine Power: kW (hp)
-Standby: 544.0 (730.0) &nbs